B846 Specifications

Inputs:

Start (B846-500/100): NPN or Dry Contact
Reset (B846-500/100): NPN or Dry Contact

Outputs:

Timed (B846-500/100): DPDT - 5 amp
Timed (B846-511): SPDT - 5 amp
Instantaneous (B846 -511): SPDT - 5 amp
Operation:
Supply Voltage: 24 - 240 VAC 50/60Hz, and 24 VDC
Power Consumption: < 10 VA
Time Ranges: Field Selectable 1, 10 Seconds; 1, 10 Minutes; 1, 10 Hours
Operating Modes: On-Delay, Off-Delay, Interval, Repeat (B846-500/511), Delay Interval (B846-100)
Setting Accuracy: + 5%
Repeat Accuracy: + 0.5%
Electrical Service Life: 100,000 cycles at full load
Mechanical Service Life: 10 million cycles at min. load
Environmental:
Front Panel Rating: NEMA 4X/IP65
Operating Temperature: 0° to 55° C (32° to 131° F)
Storage Temperature: -40° to 90° C (-40° to 194° F)
Humidity: 5% to 95% RH non-condensing
Weight: 100 grams (3.5 ounces)

Operating Modes

 On-Delay

Timing begins on the leading edge of the start input. The output will activate at the completion of the preset time (T) and will remain active until the reset signal is applied or power is interrupted.

Eagle Signal Timers
 Off-Delay

The output is activated at the leading edge of the start signal. Timing begins on the trailing edge. The output will remain active until the preset time (T) has elapsed or power is interrupted. Reapplying the start signal before T has elapsed will reset the time value. The reset input is not used.

Eagle Signal Timers
 Interval

On the leading of the start input, the output is activated and timing begins. The output will remain active until the preset time (T) has elapsed or power is interrupted. Removal of the start signal will also cause the ouput to be deactivated and the time value reset. The reset input is not used.Interval

Eagle Signal Timers
 Repeat Cycle

Timing begins upon application of power. A cycle is initiated where the output will be OFF for the preset time (T), then ON for the preset time. This cycle will continue until a reset signal is applied or power is interrupted. If the start signal is present upon power-up, the cycle will be inverted with the ON phase proceeding the OFF phase.

Eagle Signal Timers
 On-Delay/Interval

Timing begins on the leading edge of the start signal. The output turns ON when the delay preset time (T1) has elapsed. The output remains ON for the duration of the interval time (T2), then turns OFF. Interval times (T2) of 0.5, 1.0, 1.25, 2.0, 2.5, 4.0, 5.0, or 10.0 seconds may be selected.

Eagle Signal Timers

 


Ordering Information 
 Description     Model
 Multi-Function Timer    B846-500
 As Above w/Instant Contacts     B846-511
 With On-Delay/Interval Timer     B846-100
     Accessories
 Mounting Bracket & Locking Ring     B846-A30
 8 Pin Socket     60SR2P06
 11 Pin Socket     60SR3P06 


Download The Complete B846 Technical Manual (55 kb .pdf file)

 